Inspectors do walk into AHU plant rooms, and a puddle under a drain pan says more about maintenance than the SOP does.
EU GMP Chapter 3 expects premises and equipment to be suitable and maintained. Chapter 4 expects logbooks for critical equipment and processing areas; most sites include the plant room.
Water under a cooling coil usually traces back to the condensate trap. On a draw-through unit the coil section runs below atmospheric pressure, and the trap's water seal has to be deeper than that suction or the fan holds the condensate in the pan. At −600 Pa in the section, that is about 61 mm of water before any margin. A trap built to a standard detail and never checked against fan static pressure explains a lot of wet insulation and rust streaks.
Labels are quicker: ducts marked supply, return or exhaust with AHU and airflow direction, valve tags matching the P&ID. Each filter pressure gauge should carry a calibration label in date, ideally with the change limit marked on its face. The logbook, paper at the unit or entries in the CMMS, should show the last filter change and the last fan check with a date and a name.
Stored boxes, spare filters leaning on the casing and a chair with a kettle belong somewhere else.