Cable tables assume 30 °C air. A roof plant room in Ho Chi Minh City in April is not at 30 °C.
The current ratings in IEC 60364-5-52 are tabulated for a reference ambient of 30 °C in air. Anything hotter needs a correction factor, and at 40 °C the standard's table gives 0.87 for PVC insulation and 0.91 for XLPE. A PVC cable the table rates at 100 A is an 87 A cable in that room.
Then count its neighbours. Cables in a full tray heat each other, and the same standard gives a reduction factor for grouped circuits. Six circuits touching in a single layer on a perforated tray take 0.73. The two factors multiply: 100 A × 0.87 × 0.73 is about 64 A.
Load that cable to 100 A and nothing trips. The insulation runs above its rated temperature and ages faster, and the failure turns up years later with no obvious link to the design.
The fix is in the cable schedule. For each route, write the ambient temperature used and where it came from: a measurement, or the plant room's design maximum. Write the installation method and the number of grouped circuits. Apply both factors, choose the size, then check voltage drop. Ceiling voids above cleanrooms deserve the same treatment as the roof: they are not air-conditioned either.
What ambient does your cable schedule state for the roof plant room?