In a Grade C room at 20 air changes an hour, perfect mixing gives a 100:1 recovery time of about 14 minutes.
The supply terminal decides how far a real room falls short, because mixed-flow rooms clean themselves by dilution. For ideal mixing the 100:1 recovery time is ln(100) divided by the air change rate, so 4.6 / 20 of an hour, or 13.8 minutes. A corner the supply air only half reaches can behave like a room at 10 air changes, and the same sum gives about 28 minutes.
Swirl diffusers come closest to the ideal. They throw air out radially and pull a lot of room air into the jet, which evens out concentrations, at the cost of some turbulence at head height and more noise at high flow. Perforated face plates induce less and tend to leave slower spots between terminals, most of all where low-level returns are far apart.
Take the diffuser plate away and a HEPA terminal sends a low-velocity plume straight down. Over a critical bench that can be the right choice, because directly underneath is very clean. Repeated along a whole Grade C corridor, the plumes do not spread far and the corners catch up slowly.
This is why the probe position in the ISO 14644-3 recovery test matters. A probe under a terminal reports the best figure in the room. Place it where the smoke study shows the air arriving last.