A 3 m high cleanroom with 100 W/m² of sensible heat needs about 12 air changes to stay cool, at an 8 K supply difference.
The arithmetic is the sensible heat equation. Airflow = heat ÷ (density × specific heat × ΔT) = 100 ÷ (1.2 × 1,005 × 8) ≈ 0.0104 m³/s per m² of floor, about 37 m³/h. Over a 3 m ceiling that is roughly 12 ACH.
If the cleanliness class and recovery target call for 40 ACH, the other 28 are there for dilution only. They carry no cooling duty, yet in many designs every one of them is pushed through the central AHU: pre-filters, coil, reheat, long ductwork, terminal HEPA. Fan power follows airflow times pressure, so the dilution air pays the full pressure drop of a system it does not need.
The alternative is to split the duty. The central unit handles the 12 ACH that does the thermal and humidity work plus the fresh air. A secondary recirculation loop, or fan filter units in the ceiling, moves the dilution air at a much lower pressure.
It is not free. FFUs add motor heat inside the room and many small fans to maintain, and a recirculation loop needs space. Which way wins depends on the room size and the hours it runs. But the question should be asked before the AHU is sized, not after the energy bill.



