Forty fan filter units over one Grade C room give you forty speed settings, and the room total is right only while every one of them holds.
The alternative is ducted terminal HEPA fed from one AHU. Both can reach the grade. We would weigh airflow control first.
In a ducted system one fan speed and a few dampers at the AHU hold the total supply. An FFU ceiling has no single point that sets the total; each unit is its own supply. Group control of EC motors helps, but the balance is still checked at each requalification.
On energy, the fan-heat argument is weak. The heat reaches the air either way: an FFU releases it in the plenum, and the fan in a draw-through AHU adds it just after the coil. What differs is fan efficiency and pressure drop. Small FFU motors are usually less efficient than one large AHU fan, but FFUs skip the duct and terminal losses. Which uses less depends on the layout, so calculate it. Retrofits without duct space often favour FFUs.
One failed FFU leaves one zone short of supply. An AHU fan stopping takes out the whole area unless the fans sit in a fan wall with redundancy. An FFU ceiling still depends on a make-up AHU for fresh air, cooling and dehumidification, and if that unit stops the room loses pressurisation too.