In a multi-product OSD plant, the cross-contamination path nobody draws is the return duct.
Two granulation suites on one recirculating AHU look separate on the layout. Different rooms, airlocks, pressure cascade, gowning. Then the return air from both rooms meets in the same duct, passes the same filters and comes back as supply. The rooms are connected by the air handling, whatever the architecture says.
Whether that is acceptable depends on three things: how dusty the operations are, how potent the products are, and what sits between the return and the supply. The choices, roughly from cheapest to most expensive:
- Dust extraction at source, so less reaches the return at all.
- HEPA filtration in the recirculation path. EN 1822 H13 is rated at 99.95% at MPPS and H14 at 99.995%, with the extra pressure drop and a filter change that has to be contained for potent products.
- A dedicated AHU per suite or per product group.
- Once-through air for the dustiest rooms, which in a tropical climate means paying to dehumidify every cubic metre of fresh air.
Annex 1 is written for sterile products, but its habit of a Contamination Control Strategy works just as well here. If the CCS says how products are kept apart, it has to say it for the air handling too, with the AHU zoning drawing attached.