Duct airtightness classes: each step is 3× tighter

  • News
  • 1 min read

Each step in duct airtightness class, from A to D, allows about a third of the leakage of the class before it.

The European duct standards express the limit as a leakage factor times the test pressure to the power 0.65, in litres per second per square metre of duct surface. The factor is 0.027 for class A, 0.009 for B, 0.003 for C and 0.001 for D. Each is a third of the one before, so every step is 3× tighter.

In numbers: at 400 Pa, 500 m² of class B ductwork may leak about 220 l/s. The same duct in class C, about 75 l/s. That is roughly 800 m³/h against 270 m³/h, from a duct that passed its test either way.

Leakage upstream of the terminals costs fan energy; balancing covers it. The leakage that moves a cascade is downstream of where the flow is controlled. If a constant-volume box measures the air and the duct after it leaks into the ceiling void, the controller is satisfied and the room is short. On the return side, a leaking duct draws void air instead of room air, and the room pressure drifts up in a way the balancing report never showed.

So the class matters most on the short runs between the flow control point and the room. Our habit is class C or better on ductwork serving a pressure cascade, and a leak test on those sections before they disappear above the ceiling.

What airtightness class does your current duct specification call for?

Related

More on this subject

Energy savings and the requalification bill

Energy measures that change validated cleanroom conditions go through Annex 15 change control. Classification alone can mean 10 sample locations for a 50 m² room, at rest and in operation, before recovery tests and a CCS update. Price that next to the kWh, or design reduced modes in and qualify them once.

InsightRead

EU GMP Chapter 3 and 21 CFR 211 on HVAC

21 CFR 211.42 and 211.46 and EU GMP Chapter 3 ask for adequate ventilation, air control and filtration, but give no air change rate or pressure differential, and no filter class beyond HEPA for aseptic areas. Those come from Annex 1, FDA's 2004 aseptic guidance, ISO 14644 and the designer's justification, recorded in the design basis.