Each step in duct airtightness class, from A to D, allows about a third of the leakage of the class before it.
The European duct standards express the limit as a leakage factor times the test pressure to the power 0.65, in litres per second per square metre of duct surface. The factor is 0.027 for class A, 0.009 for B, 0.003 for C and 0.001 for D. Each is a third of the one before, so every step is 3× tighter.
In numbers: at 400 Pa, 500 m² of class B ductwork may leak about 220 l/s. The same duct in class C, about 75 l/s. That is roughly 800 m³/h against 270 m³/h, from a duct that passed its test either way.
Leakage upstream of the terminals costs fan energy; balancing covers it. The leakage that moves a cascade is downstream of where the flow is controlled. If a constant-volume box measures the air and the duct after it leaks into the ceiling void, the controller is satisfied and the room is short. On the return side, a leaking duct draws void air instead of room air, and the room pressure drifts up in a way the balancing report never showed.
So the class matters most on the short runs between the flow control point and the room. Our habit is class C or better on ductwork serving a pressure cascade, and a leak test on those sections before they disappear above the ceiling.
What airtightness class does your current duct specification call for?