Charged media: new efficiency vs discharged efficiency

  • News
  • 1 min read

A synthetic bag filter can test very well on day one and lose much of that efficiency in service, while its pressure drop hardly moves.

The reason is electrostatic charge. Many synthetic media are charged, and the charge pulls in fine particles the fibres alone would miss. In service, fine dust coats the fibres and the charge drains away. The filter still looks clean on the gauge. It is just filtering less.

The standards caught up with this in two steps. EN 779:2012 added a minimum efficiency, measured after discharge, for F7, F8 and F9: 35%, 55% and 70% at 0.4 µm. ISO 16890 went further. Part 4 strips the charge from a test sample with isopropanol vapour, and Part 1 rates ePM efficiency as the average of the initial and the discharged result. So the number on an ISO 16890 label sits between the day-one filter and the fully discharged one. In our view it is a fairer guide to month six than to the delivery day.

Two practical consequences for a GMP plant. Buy pre-filters on their ISO 16890 ePM1 rating, not on a supplier's initial efficiency curve. And do not read a low pressure drop as proof that a stage is working. A discharged pre-filter passes more fine dust to the next stage, and the HEPA downstream loads faster.

Topics

Related

More on this subject

Clean build protocol: staged rules and a gate before each

Dust built into a cleanroom is slow to remove. A clean build protocol stages the rules: dirty work first, then a closed envelope with no cutting inside, HVAC on temporary filters, a final clean with gowning, and terminal HEPA filters fitted last. Each stage needs an inspection and a signature before the next begins.

InsightRead

Manufacturing & Distribution

Clean the new AHU before its first fan run

A new AHU started during construction loads its coil, drain pan and final filters with site dust that does not vacuum off wet fins. Clean the casing before power-on, seal duct openings, run on temporary pre-filters, fit final filters after the final clean and record it for IQ.

InsightRead