Three rooms in a cascade, each pressure sensor good to ±1 Pa.
Measured room to room, the innermost room against the corridor carries up to ±3 Pa of error.
A pressure cascade can be measured two ways, and each one hides its error in a different place.
The first puts every room against one common reference, usually the corridor or a point outside the suite. Errors do not stack, since each reading carries one sensor's error. The catch is the difference between two adjacent rooms, which has to be computed from two readings and so carries up to ±2 Pa. Against a 10 Pa design differential, that is a fifth of the value.
Direct sensors across each door give you the differential that sets airflow direction between rooms, which is what Annex 1 expects to be monitored, with one sensor's error on it. The weak point moves to the end of the chain: the innermost room against the reference is a sum of readings, and the errors add up with it.
Neither scheme is wrong. A good system records one set, computes the other, and states the error budget for both, so no alarm limit is set tighter than the measurement can resolve.
The scheme belongs in the design basis beside the setpoints, where the BMS engineer and the validation team read the same numbers. Humiley designs cleanroom pressure cascades for Grade A to D suites.