Same ePM1 rating, different energy use

  • News
  • 1 min read

Between two ePM1 70% filters, a 50 Pa difference in average pressure drop costs about 2,000 kWh a year on a 10,000 m³/h AHU.

ISO 16890 tells you what a filter captures. It says nothing about the pressure drop it takes to do that over its life. Eurovent's energy efficiency classification fills the gap: filters are rated from A+ down to E on a calculated annual energy use at a reference airflow and a standard dust loading, so two ePM1 filters with the same efficiency can be compared on what they cost to run.

The mechanism is fan power: airflow times pressure drop, divided by fan system efficiency. Take 10,000 m³/h, a fan system efficiency of 60%, and two filters whose average pressure drop over their life differs by 50 Pa. That is 2.78 m³/s × 50 Pa / 0.6, about 230 W, all year. Over 8,760 hours, about 2,000 kWh.

A class on a datasheet is a comparison at reference conditions, not your plant. Your airflow, the wet-season dust load and your change interval move the real figure. The classes still rank filters on one test, which a unit price does not.

With the next filter quote, ask for two things: the Eurovent certificate and energy class, and the initial and final pressure drop at your airflow.

Related

More on this subject

See the filters without stopping the fan

A pressure gauge shows filter loading but not a collapsed bag, a slipped gasket or a wet drain pan. Viewing windows and internal lights in the filter, coil, humidifier and fan sections let technicians check with the unit running. Double-glaze windows on cold sections, and keep the doors for checks that need a stop.

InsightRead

Manufacturing & Distribution

Set AHU door swing by casing pressure

On positive-pressure AHU sections an outward-opening door is pushed off its gasket while the fan runs, so those doors should open inward and doors on negative sections outward. Where a positive-side door must open outward, fit a two-stage safety latch. Mark swing and latch type on the GA drawing, section by section.

InsightRead