Holding ±2% RH starts with where the sensor sits

  • Maintenance Service
  • 1 min read

At 21 °C and 50% RH, a sensor reading 0.5 K warm reports humidity about 1.5% RH low.

Against a ±2% RH band, that leaves little for the equipment.

Near room conditions RH moves by roughly 3% RH per kelvin at 50%, because it depends on temperature as much as on moisture. A dehumidifier that can hold ±2% RH will only do it if the sensor sits at the room's temperature and sees the room's air quickly. Add a transmitter accuracy of ±1.5% RH and most of the band is spoken for before drift.

Where it tends to go wrong:

  1. A wall sensor near a door, a heat source or a supply diffuser reads its corner, and its corner's temperature, rather than the room.
  2. A sensor in the return duct reads the mixed average and sees changes late, so the loop reacts to what happened a few minutes ago.
  3. A slow sensor, or one inside a housing with little airflow, adds lag the tuning never accounted for, and the dehumidifier hunts.
  4. Drift between calibrations takes another slice of the band. The interval matters as much as the model.

Retuning the PID fixes none of these. They are settled at design: a location that represents the controlled zone, a short path, and a sensor class and calibration interval chosen against the band that was promised. In semiconductor micro-environments a ±2% RH band is a common requirement, and the sensor position is worth marking on the drawing.