A handover BIM model can show every AHU in the plant and still be useless to the maintenance team on day one.
The geometry is usually fine: the casing, the ducts, the clearance to pull a coil. What is missing is the data a CMMS needs. Tag numbers that match the P&ID, filter classes, motor ratings, the criticality rating, the maintenance interval. A planner then spends weeks retyping O&M manuals into the maintenance system, and the model is never opened again.
ISO 19650 sets the order. The appointing party states its information requirements before anything is modelled: organisational information requirements (OIR) for what the business needs, asset information requirements (AIR) for what each asset must carry into operation, and exchange information requirements (EIR) for what each delivery during the project must contain. The model is produced to meet them.
For a GMP plant, draft the AIR with three readers in mind five years on: the maintenance planner, the validation team and the QA reviewer. Between them they need the tag, location, system boundary, impact classification and the document that qualified each item. Those fields belong in the AIR before the first duct is drawn.