An isolation room held negative runs two different airflows, and the 12 air changes an hour in the brief belong to one of them.
Take a 4 × 5 × 3 m room: 60 m³. Twelve air changes an hour is 720 m³/h. To hold the room negative to its anteroom, exhaust is set above supply, say by 100 m³/h, and the difference is drawn in under and around the door.
Count the 12 on supply and the room gets 720 m³/h in and 820 m³/h out, about 13.7 air changes by exhaust. Count it on exhaust and supply drops to 620 m³/h, about 10.3 air changes of clean air reaching the patient. Same room, same offset, and 100 m³/h between the two readings.
The rate itself comes from the hospital guideline the project follows. ASHRAE 170, a common reference, lists 12 total air changes an hour for an airborne infection isolation room; national guidelines set their own. Which airflow the number applies to belongs in the design brief, with the edition, before a balancing contractor has to pick one on site.
Where the brief is silent, sizing supply to the full rate and letting exhaust carry the offset on top settles it. The cost is 100 m³/h of cooled air thrown away, and the room meets the number whichever way a reviewer divides.
Isolation rooms sit in our hospital work, where pressurisation is engineered as infection control.
Has a balancing contractor on one of your hospital projects ever had to guess?