Lab ventilation: one fume hood sets the airflow

  • Life Sciences
  • 1 min read

One fume hood with a 1.8 m sash open 0.5 m, held at 0.5 m/s face velocity, exhausts about 1,620 m³/h.

In a QC lab of 180 m³ that single hood is 9 air changes an hour, before anyone has thought about occupancy. Add three more hoods and the hoods are the design. Nearly all of that exhaust comes back as make-up supply. In Viet Nam most of it is outdoor air that has to be cooled and dried first; some can be transfer air from the corridor, which is also how the lab stays negative.

A constant-volume hood pulls that 1,620 m³/h whether the sash is open or shut. A variable-volume hood cuts exhaust as the sash comes down. At 0.25 m the same hood needs about 810 m³/h to hold 0.5 m/s, down to the minimum flow the hood maker sets. The saving only arrives if people close their sashes.

On a variable-volume lab we would test the tracking first. Supply follows exhaust with a fixed offset to keep the room negative to the corridor. If a sash sensor fails or an exhaust flow sensor drifts, the hood can run below its face velocity, and unless it has its own face velocity alarm nobody at the bench knows. Or the offset closes and the lab goes neutral. At commissioning, disconnect the sensor and watch the hood alarm and the room pressure.

Humiley designs lab ventilation as part of its Life Sciences work.

Industries

Related

More on this subject

Three PPQ batches: where the number has to come from

EU GMP Annex 15 (2015) treats three consecutive PPQ batches as a common minimum, with the number justified from risk; the FDA's 2011 guidance names no count and works in three stages. A rationale that serves both draws on commercial-scale variability, parameters near their proven limits, prior knowledge and a statistical target on the CQAs.

InsightRead