If the access zone isn't dimensioned on the AHU general arrangement drawing, someone will fill it with a cable tray.
An AHU is designed once and then maintained for decades. Three routine tasks need space that nobody draws by default:
- Bag and HEPA filters have to come out straight, without tilting through a gap narrower than the filter. Side withdrawal or front access decides which side of the unit must stay clear.
- Coils slide out sideways for cleaning or replacement, so the pull side needs clear space roughly equal to the coil length. Put that side against a wall and the next coil replacement means opening up the casing.
- EC fans in a fan wall come out one at a time through the access door, but only if the door is big enough and there is somewhere to put the fan down. Larger plug fans need a lifting point above them.
On the AHU GA these zones belong as dimensioned volumes, carried into the BIM model, where other trades see them as obstacles instead of empty space.