A filling line changed in March can still run on an SOP that passed its scheduled review in May with no edits.

EU GMP Chapter 4 asks for documents to be reviewed regularly and kept up to date, and gives no interval. Many sites write 2–3 years into the document control SOP. That is defensible if the procedure also names the events that pull a review forward:

  1. A change control on the equipment, system or room the SOP covers.
  2. A deviation or CAPA whose root cause points at the procedure, including a second "SOP not followed" finding on the same step.
  3. A change to something the SOP relies on, such as a new disinfectant added to the approved list, or a revised environmental monitoring SOP that moves the sampling points in the room.
  4. An audit or inspection observation on the process, or a regulatory update.
  5. A new product brought into the room.

The scheduled review can be made to earn its signature as well. Before approving, the reviewer pulls the change log and the deviation log for the room since the last approval and reads the SOP against both. If they are empty and the text still matches the floor, a re-approval with no edits is a fair result.

Humiley's EU-GMP roadmap consulting covers setting up the QMS these procedures live in.

How we support quality system set-up

Industries

Related

More on this subject

A BMS setpoint edit is a GMP change

Moving a room pressure setpoint from 15 Pa to 12 Pa changes nothing physical and still changes a qualified parameter. Annex 15 section 11 and Annex 11 put it under change control: raise it, assess the cascade and the CCS, decide on retest, then edit. Lock qualified setpoints behind a controlled role.

InsightRead

Annex 11: accuracy checks on manual entries

The 2011 text of EU GMP Annex 11 (clause 6) says that where critical data are entered manually there should be an additional check on their accuracy, by a second operator or by validated electronic means. For a BMS or EMS alarm limit, a permitted range on the field and a confirmation step are the practical answer.

InsightRead