Reading BMS trends for simultaneous heating and cooling

  • News
  • 1 min read

Some reheat is the price of dehumidification. The rest is waste, and the BMS trends show which is which.

A cleanroom AHU in a humid climate cools air below the room dew point to dry it, then warms it back up. That reheat is designed in. The trouble is a unit that cools and heats against itself all year, well beyond what drying needs. Pull these trends for one normal week, per AHU:

  1. Cooling valve and reheat valve positions together. Both well open at steady load, hour after hour, is the first sign.
  2. Supply air dew point against the lowest dew point any room on the unit needs. If the supply is several degrees drier, the coil is over-drying and the reheat pays for it.
  3. Heating and cooling setpoints, room by room. Overlapping setpoints, or no dead band between them, set two loops against each other.
  4. Air temperature before and after each coil while its valve reads 0%. A change across a closed coil means the valve passes.
  5. The same four at 02:00 on a Sunday. If the pattern matches Tuesday at noon, the unit is not following the load.

The usual fixes are cheap next to the energy: a dew point setpoint reset to what the rooms need, a dead band, a valve reseated.