Some reheat is the price of dehumidification. The rest is waste, and the BMS trends show which is which.
A cleanroom AHU in a humid climate cools air below the room dew point to dry it, then warms it back up. That reheat is designed in. The trouble is a unit that cools and heats against itself all year, well beyond what drying needs. Pull these trends for one normal week, per AHU:
- Cooling valve and reheat valve positions together. Both well open at steady load, hour after hour, is the first sign.
- Supply air dew point against the lowest dew point any room on the unit needs. If the supply is several degrees drier, the coil is over-drying and the reheat pays for it.
- Heating and cooling setpoints, room by room. Overlapping setpoints, or no dead band between them, set two loops against each other.
- Air temperature before and after each coil while its valve reads 0%. A change across a closed coil means the valve passes.
- The same four at 02:00 on a Sunday. If the pattern matches Tuesday at noon, the unit is not following the load.
The usual fixes are cheap next to the energy: a dew point setpoint reset to what the rooms need, a dead band, a valve reseated.