With a ring main unit at the incoming 22 kV substation, a faulted cable section can be switched out instead of waiting for the repair.
On a radial feed there is only one path, so a cable fault holds the plant until the cable is fixed. The ring main unit (RMU) closes the loop: the plant can be fed from either end, and the damaged section is isolated by switching.
What sits inside is short to describe:
- Load-break switches on the incoming and outgoing ring cables.
- For the transformer, either a fuse-switch combination or a circuit breaker with a protection relay.
- On each way, an earthing switch interlocked with the main switch, so nobody works on a cable that can still be energised.
- Next to it, a metering cubicle with CTs and VTs that the utility seals, at the agreed point where their ownership ends and yours starts. Settle that point early, because it fixes the room layout.
The ring does not stop the outage. The plant is still dark while the fault is located and switched out, and how long that takes depends on who operates the ring, the utility or the plant, and whether they switch remotely or by hand at the substation. Plan the cleanroom restart sequence for that gap, and keep the BMS and environmental monitoring on backed-up power so the event is recorded.