Ring main units for a 22 kV plant supply

  • News
  • 1 min read

With a ring main unit at the incoming 22 kV substation, a faulted cable section can be switched out instead of waiting for the repair.

On a radial feed there is only one path, so a cable fault holds the plant until the cable is fixed. The ring main unit (RMU) closes the loop: the plant can be fed from either end, and the damaged section is isolated by switching.

What sits inside is short to describe:

  1. Load-break switches on the incoming and outgoing ring cables.
  2. For the transformer, either a fuse-switch combination or a circuit breaker with a protection relay.
  3. On each way, an earthing switch interlocked with the main switch, so nobody works on a cable that can still be energised.
  4. Next to it, a metering cubicle with CTs and VTs that the utility seals, at the agreed point where their ownership ends and yours starts. Settle that point early, because it fixes the room layout.

The ring does not stop the outage. The plant is still dark while the fault is located and switched out, and how long that takes depends on who operates the ring, the utility or the plant, and whether they switch remotely or by hand at the substation. Plan the cleanroom restart sequence for that gap, and keep the BMS and environmental monitoring on backed-up power so the event is recorded.

Humiley designs LV–MV power distribution up to 22 kV together with the HVAC it feeds.

Talk to an engineer: contact@humiley.com · +84 28 7777 6668 (Viet Nam office)

Related

More on this subject

Three APS runs across all shifts, and the HVAC has to hold still

Annex 1 initial validation of an aseptic process needs at least 3 consecutive successful simulations covering all working shifts, then periodic runs twice a year per process, line and shift. The cleanroom must hold its qualified state throughout. Agree an HVAC freeze date with QA, and list in advance which jobs are like-for-like and which need an impact assessment.

InsightRead

Value engineering after tender: savings that return at OQ

After an over-budget cleanroom HVAC tender, three savings recur: an EN 1886 L2 casing instead of L1, fewer room pressure transmitters, and deleted door drop-seals. Each can reappear as an OQ failure in airflow, alarm testing or pressure differentials, so check every line against its URS requirement and test before accepting it.

InsightRead