A 70%-effective sensible heat exchanger recovers about 14% of the outdoor-to-exhaust gap on a humid Ho Chi Minh City afternoon.
Take outdoor air at 29 °C with a 26 °C dew point, and cleanroom exhaust at 20 °C and 45% RH. The outdoor air carries about 83.7 kJ/kg; the exhaust about 36.7. The gap is roughly 47 kJ/kg, and that is what the fresh-air coil has to remove if nothing is recovered.
A sensible-only exchanger, plate or run-around, works on the 9 K temperature difference. At 70% effectiveness it takes about 0.7 × 9 × 1.03 ≈ 6.5 kJ/kg off the incoming air. That is 14% of the gap.
The rest is moisture. The outdoor air holds around 21 g/kg, the exhaust around 6.5 g/kg. Only an enthalpy exchanger moves that, usually a wheel or a membrane plate, and with it comes the risk of exhaust air carrying over into the supply, which QA will ask about.
The supply side of the exchanger runs below the 26 °C dew point, so it condenses. Part of the recovered 6.5 kJ/kg leaves as water, and the plate or coil needs a drain pan, a fall to drain and cleanable surfaces, like any cooling coil.
On a large fresh-air system, 6.5 kJ/kg is still a useful number of kilowatts; payback depends on airflow, hours and tariff. A study that assumes temperate recovery figures will overstate it. Cutting the fresh-air volume, or drying it less deeply where the product allows, usually saves more.