The peak-load spreadsheet tells you how big the coil, fan and chiller must be. It says nothing about where the energy goes over a year.
A year has 8,760 hours. In a tropical cleanroom most of them are part-load hours: the sensible load is low, the latent load is still high, and the system cools air to dry it, then reheats it to hold room temperature. In southern Viet Nam the wet season runs roughly from May to November, around 5,000 hours in which that overcool-and-reheat pattern can dominate. A design-day sheet shows none of it.
An hourly model runs every one of those hours against a weather file for the site, with the real control sequence: what the coil valve, the reheat, the fan speed and the chiller staging do each hour. ASHRAE 90.1 Appendix G uses this kind of annual hourly simulation to compare a proposed design with a baseline.
Reheat is where design options pull apart. Condenser heat recovered for reheat, or a dedicated fresh-air unit so the recirculation coils can run warmer, can look marginal on the peak sheet and large across a wet season. A percentage target works the same way: Humiley's energy modeling targets a 30% reduction in HVAC energy, and any figure like that is measured against a baseline run over the same hours.