Size with a spreadsheet, test energy with an hourly model

  • News
  • 1 min read

The peak-load spreadsheet tells you how big the coil, fan and chiller must be. It says nothing about where the energy goes over a year.

A year has 8,760 hours. In a tropical cleanroom most of them are part-load hours: the sensible load is low, the latent load is still high, and the system cools air to dry it, then reheats it to hold room temperature. In southern Viet Nam the wet season runs roughly from May to November, around 5,000 hours in which that overcool-and-reheat pattern can dominate. A design-day sheet shows none of it.

An hourly model runs every one of those hours against a weather file for the site, with the real control sequence: what the coil valve, the reheat, the fan speed and the chiller staging do each hour. ASHRAE 90.1 Appendix G uses this kind of annual hourly simulation to compare a proposed design with a baseline.

Reheat is where design options pull apart. Condenser heat recovered for reheat, or a dedicated fresh-air unit so the recirculation coils can run warmer, can look marginal on the peak sheet and large across a wet season. A percentage target works the same way: Humiley's energy modeling targets a 30% reduction in HVAC energy, and any figure like that is measured against a baseline run over the same hours.

Related

More on this subject

Three APS runs across all shifts, and the HVAC has to hold still

Annex 1 initial validation of an aseptic process needs at least 3 consecutive successful simulations covering all working shifts, then periodic runs twice a year per process, line and shift. The cleanroom must hold its qualified state throughout. Agree an HVAC freeze date with QA, and list in advance which jobs are like-for-like and which need an impact assessment.

InsightRead

Manufacturing & Distribution

Two envelopes for a cleanroom HVAC tender

Score the technical envelope of a cleanroom HVAC tender and sign it off before any price is opened. Issue the scoring sheet with the tender: mandatory items pass or fail, the rest weighted, for example 40% technical depth and 20% each for documentation, delivery and service. Score every listed deviation.

InsightRead