  • News
  • 1 min read

3.6 mA or below, or 21 mA or above: under NAMUR NE 43, that loop current is the transmitter reporting its own fault.

The EMS has to read it that way. If it holds the last good value instead, a broken wire shows a steady room for as long as nobody checks, and the batch record looks clean. None of it is data.

A valid measurement sits between 3.8 and 20.5 mA. Set each transmitter's fail direction, then configure the input cards and the EMS to read those currents as bad quality, raise an alarm, and show a gap or a flag on the trend. Never substitute the last good reading.

Digital links need the same thinking. A Modbus or OPC value that stops updating still shows a number. Check the timestamp, alarm on communication loss, and treat a value that has not moved by a single digit for hours as suspect. A real room pressure differential always wanders a little.

ALCOA+ asks for accurate records, and a frozen number shown as a live one fails that however stable it looks.

In the monitoring systems we design, NE 43 behaviour and stale-value detection go into the functional specification, and OQ tests them the simple way, by pulling a wire.

Talk to an engineer: contact@humiley.com · +84 28 7777 6668 (Viet Nam office)

Related

More on this subject

ALCOA+ on a paper pressure log

A paper room-pressure log with every reading in the same pen at the end of the shift fails ALCOA+ before any number is checked. Walking one sheet against the nine attributes, from attributable initials to enduring ink, shows that most data-integrity failures are fixed by redesigning the form.

InsightRead

Four checks at the basic-design gate

Before detail design opens, a GMP project should have frozen room data sheets and pressure cascade, loads that match the equipment list, a URS for each critical system and owned open items. A cascade change after the ducts are drawn reaches the duct sizes, terminal filters, AHU selection and every neighbouring pressure step.

InsightRead