Sink or bubble: when product and operator both need protecting

  • Life Sciences
  • 1 min read

GMP wants air to flow out of the clean room. Biosafety wants it to flow into the room that holds the organism.

A live-organism suite has to satisfy both.

Product protection puts the processing room highest. Containment puts the room with the organism lowest, so leaks run towards it and away from the corridor. One cascade direction for the whole suite gives up one of the two, so the compromise is carried by the airlock between room and corridor.

A sink airlock is held below the room and the corridor. Air enters from each side and leaves through the airlock's own exhaust. Room air cannot reach the corridor, and the room can still sit positive to its airlock for the product.

In a bubble arrangement the airlock is held above both neighbours on clean supply air, which spills into the room and into the corridor. Air from the room cannot travel past it to the corridor, and corridor air cannot reach the room. It costs more supply air, and the room sits below its airlock.

In both cases the containment argument rests on the door interlock. With both doors open, the airlock separates nothing and air moves between room and corridor from whichever side is higher. The risk assessment should say what happens then, and who the alarm reaches.

Each step needs a measurable differential, typically 10–15 Pa between adjacent grades, with Annex 1 guidance of at least 10 Pa.

Topics

Industries

Related

More on this subject

Three APS runs across all shifts, and the HVAC has to hold still

Annex 1 initial validation of an aseptic process needs at least 3 consecutive successful simulations covering all working shifts, then periodic runs twice a year per process, line and shift. The cleanroom must hold its qualified state throughout. Agree an HVAC freeze date with QA, and list in advance which jobs are like-for-like and which need an impact assessment.

InsightRead

WFI belongs in the Contamination Control Strategy

EU GMP Annex 1 (2022) gives WFI circulation above 70 °C as an example of minimizing the risk of microbial growth. Keeping a loop hot drives the design: ASME BPE dead legs of L/D ≤ 2, turbulent flow to the last user point, planned sanitization and sensors on the return. The CCS should justify all of it.

InsightRead