Going from 10 to 20 Pa across a cleanroom door adds about 41% to the air leaking through its gaps, and real cracks leak closer to 57% more.
The 41% comes from the orifice equation, Q = Cd·A·√(2ΔP/ρ). Flow through door gaps, cable penetrations and panel joints rises with the square root of pressure, so doubling ΔP gives √2, about 1.41 times the leakage.
Narrow cracks add friction that a sharp-edged opening does not have, and measured building leakage fits a flow exponent nearer 0.65 than 0.5. With n = 0.65, 2^0.65 ≈ 1.57.
The extra air leaves the room as treated supply, already cooled and dried for a tropical climate and filtered at the terminal, and the AHU has to make it up. On a long cascade the step repeats at every door.
Annex 1 guidance asks for at least 10 Pa between adjacent grades, and 10–15 Pa is the usual design range. Some rooms do justify more. A containment suite may need a bigger step, and so may a room where transducer tolerance takes a good part of a 10 Pa margin. Write that reason into the design basis next to the number. Setting 20 or 30 Pa because higher feels safer mostly buys leakage air and heavier doors.
We set cascade values from the room data sheets and a leakage estimate, and argue them in the CCS.