A room pressure setpoint goes from 15 Pa to 12 Pa. The SCADA log records the user, the time and 12 Pa. The 15 is gone.
That log fails 21 CFR 11.10(e) on one phrase: record changes shall not obscure previously recorded information. An audit trail that keeps only the new value tells an inspector that something changed and hides what it changed from. For a GMP parameter, the old value is exactly what they want to see.
The same clause asks for secure, computer-generated, time-stamped audit trails that independently record operator entries and actions that create, modify or delete electronic records, kept for at least as long as the records themselves. Three tests we would run on any BMS, EMS or SCADA before OQ:
- Change a GMP setpoint and read the trail. Old value, new value, user, date and time should all be there.
- Try to edit or delete a trail entry with administrator rights. The system should refuse, or record the attempt.
- Compare how long the trail is kept with the retention period of the batch records it supports.
EU GMP Annex 11 also expects the reason for a GMP-relevant change to be documented, so a system sold into both markets needs a reason field as well.
Humiley designs automation and SCADA to 21 CFR Part 11 and Annex 11. Writing the audit trail into the URS costs far less than adding it after FAT.