A room recovery test with a 20-minute acceptance limit, traced to a URS requirement of 15 minutes. It passed and was signed.
All that result shows is that recovery took under 20 minutes. The requirement is still unproven, and the matrix hides it well. Read in the direction it was built, from requirement to test, the row looks complete: requirement, design element, test, result. The gap only shows when you start at the test and put its acceptance criterion next to the requirement it claims to cover.
Inspectors tend to work in that direction. They pick a result and ask which requirement it proves. The same read turns up orphan tests too, protocols run and signed that are tied to no requirement at all. They cost time and add nothing to the argument.
The forward read still earns its place. It finds the requirement nobody tested, such as a humidity limit that made it into the URS and never into an OQ protocol.
GAMP 5 Second Edition (2022) is the usual reference for requirements traceability on computerized systems, and the same logic applies to HVAC and cleanroom qualification. Our design work keeps every decision traceable from requirement to calculation, drawing and test.
Try three signed results picked at random: trace each back and compare its acceptance criterion with the requirement's limit.