Transmitter range decides your cascade error

  • News
  • 1 min read

A 1% pressure transmitter ranged 0–1,000 Pa can be wrong by ±10 Pa. On a 10 Pa cascade step, that is the whole step.

Most transmitter datasheets quote accuracy as a percentage of full scale, so the error in pascals follows the span. A transmitter specified 0–50 Pa at 1% of full scale is within ±0.5 Pa, small enough to see a door seal going. Re-ranging a 0–1,000 Pa unit down to 50 Pa rarely gets you there: the base sensor error stays, and many datasheets add a turndown penalty on top.

Wide ranges get installed for understandable reasons. One part number for the whole site. A spare that fits anywhere. The cost shows up later: the BMS reads 12 Pa, the real value could be anywhere from 2 to 22, and the alarm at 8 Pa is set inside the noise.

Adjacent grades are typically 10–15 Pa apart, so a few checks are worth doing before the next requalification:

  1. Read the datasheet line. Some devices quote % of reading, some % of full scale, some add a separate zero drift, temperature effect and turndown factor.
  2. Specify room differential transmitters for the job, 0–50 Pa or ±50 Pa for most cascades.
  3. Calibrate near the working value, not only at zero and full scale.
  4. Set alarm limits with the total instrument error written next to them.

Humiley designs automation and SCADA to 21 CFR Part 11 and Annex 11, with the instrument ranges on the same design basis as the cascade.

Related

More on this subject

When the EMS server fails mid-fill

EU GMP Annex 11 (2011) clause 16 expects documented, tested continuity arrangements for systems supporting critical processes. For an environmental monitoring system that means knowing whether counters buffer and back-fill, who takes manual readings, who decides to stop a fill and how quickly the server can be restored.

InsightRead

Backup and archive are two controls under Annex 11

EU GMP Annex 11 clause 7.2 asks for regular backups whose restore is checked during validation and periodically. Clause 17 asks that archived data stays accessible, readable and intact, with retrieval re-tested after system changes. A green nightly backup does not prove that old trend data opens after an upgrade.

InsightRead