Two makers of H14 in one ceiling split the air unevenly

  • Life Sciences
  • 1 min read

Two H14 filters from a new maker, same face size, fitted beside four originals: the room's supply air no longer splits six equal ways.

In this worked example the original filters show 110 Pa initial pressure drop at rated airflow. The new maker's datasheet shows 150 Pa at the same flow. Both are H14 under EN 1822 and both seat in the housing. Where the six terminal boxes share one duct branch, air follows the lower resistance, so the four old filters carry more than their share and the two new ones carry less.

The room total barely moves, which means an air change rate worked out from the AHU flow still looks right. The velocity under the two new terminals has dropped, and if one of them sits over a filling line or a sampling point, that is where recovery time or the particle count shifts first.

A same-class substitute is still a change, and its assessment needs a number the purchase order rarely asks for: initial pressure drop at rated airflow, set against the filter being replaced. Where the two differ there are two sound options. Change the whole room's set to the new model, or retrim each box damper after fitting and measure airflow at every terminal alongside the installed leak test.

Periodic requalification and planned maintenance of GMP HVAC are part of our Maintenance Service.

See how we work

Industries

Related

More on this subject

Vibration on AHU fans: route or online sensors

Monthly route-based vibration surveys catch slow fan faults such as imbalance, misalignment and bearing wear at a low cost per point. Permanent online sensors catch faults that develop between visits. Put sensors on fans whose stop takes a Grade A or B room out of spec with no standby, and route the rest.

InsightRead