What plant steam brings into the supply air

  • Life Sciences
  • 1 min read

Plant steam fed to a humidifier lance carries whatever volatile chemical is dosed into the boiler.

Boilers are treated. Among the chemicals, neutralising amines are added to protect the condensate pipework, and they are chosen because they are volatile: they leave the boiler with the steam and neutralise the carbonic acid where it condenses. Inject that steam into an AHU and they are in the supply air.

Nobody raises it, because the steam looks clean at the lance and the water treatment contract sits with another department.

WHO's HVAC guideline for non-sterile products says humidification should be achieved by means that will not become a source of contamination. Its Part 2 is blunter: chemicals such as corrosion inhibitors or chelating agents, which could have a detrimental effect on the product, should not be added to the boiler system.

There are two ways out. One is to generate the humidification steam separately, from treated water with no volatile additives, in a clean steam generator or a steam-to-steam humidifier that uses plant steam only as its heat source. The other, where plant steam has to stay, is to get the safety data sheet of every treatment chemical and assess it against the product.

Either way the URS should state the steam quality that humidification needs.

Industries

Related

More on this subject

A CCS nobody reviews is only a snapshot

Annex 1 expects the Contamination Control Strategy to be actively reviewed and updated. A yearly meeting catches changes late. Adding one question to every HVAC change control, EM adverse trend review and deviation closure form, asking whether the CCS still says the right thing, keeps it current with the site.

InsightRead

Four checks at the basic-design gate

Before detail design opens, a GMP project should have frozen room data sheets and pressure cascade, loads that match the equipment list, a URS for each critical system and owned open items. A cascade change after the ducts are drawn reaches the duct sizes, terminal filters, AHU selection and every neighbouring pressure step.