Plant steam fed to a humidifier lance carries whatever volatile chemical is dosed into the boiler.
Boilers are treated. Among the chemicals, neutralising amines are added to protect the condensate pipework, and they are chosen because they are volatile: they leave the boiler with the steam and neutralise the carbonic acid where it condenses. Inject that steam into an AHU and they are in the supply air.
Nobody raises it, because the steam looks clean at the lance and the water treatment contract sits with another department.
WHO's HVAC guideline for non-sterile products says humidification should be achieved by means that will not become a source of contamination. Its Part 2 is blunter: chemicals such as corrosion inhibitors or chelating agents, which could have a detrimental effect on the product, should not be added to the boiler system.
There are two ways out. One is to generate the humidification steam separately, from treated water with no volatile additives, in a clean steam generator or a steam-to-steam humidifier that uses plant steam only as its heat source. The other, where plant steam has to stay, is to get the safety data sheet of every treatment chemical and assess it against the product.
Either way the URS should state the steam quality that humidification needs.