A classified room is qualified at the airflow it had during OQ, and VAV turns that airflow into a moving target.
The air change rate, the recovery time and the pressure step to each neighbour were all measured at one set of supply and extract flows. Change the flows and each of those results becomes a prediction.
So qualified rooms usually run at constant volume, meaning each room's supply and extract flows are held at their set values. The fan still varies. As filters load it has to speed up to hold the same flow, so a GMP supply AHU tends to have a variable-speed fan controlled on duct pressure or measured flow, and each room a constant-volume terminal that holds its set flow whatever the duct does.
With VAV, supply follows the cooling load. On a cool morning one room's supply falls, and its extract has to follow with the same offset or the pressure step changes size or even direction. The air change rate drops below the one the recovery test proved.
VAV still earns its place in offices, corridors outside the GMP zone, technical areas and unclassified stores, and on lab fume-hood exhaust where the supply is made to track it.
A reduced-flow setback for nights is qualified as a condition of its own, with its own pressures and recovery time: two set flows, each one proved.