The exhaust behind a solvent smell in the corridor runs through an H14 filter that passed its leak test last month.
The filter is doing what it is rated for: H14 under EN 1822 means at least 99.995% efficiency at the most penetrating particle size, a particle rating. A particle that touches a fibre stays on it, while a solvent molecule comes off again and travels on with the air.
Nor does the leak test help: it challenges the filter with an aerosol and looks for particles downstream, so vapour is not part of it. A second HEPA stage in series does nothing for the smell.
Vapours and gases need a different stage: adsorption on activated carbon or another medium chosen for the compound, or scrubbing for gases that dissolve or react. ISO 10121 is the test standard for gas-phase media and devices. Sizing starts from the compound, its concentration and the airflow, and in a humid climate from the moisture too, because water takes up capacity on carbon.
Where emission limits allow, the cheaper answer is often no treatment at all: exhaust the room once-through and discharge well away from any air intake.