A HEPA class holds at its rated flow, not above it

  • News
  • 1 min read

The EN 1822 class on a HEPA filter holds at the airflow it was tested at. Push more air through the same filter and three things move.

  1. Pressure drop rises. Flow through fibrous media is laminar, so resistance is roughly proportional to media velocity. Around 20% more air means roughly 20% more initial pressure drop, and the fan has to find it until the end of filter life.
  2. Diffusion capture falls. The smallest particles are caught because Brownian motion makes them wander into fibres. At higher velocity each one spends less time in the media and has fewer chances to hit something.
  3. The most penetrating particle size shifts smaller, and penetration at that size rises. A filter classed H14 at its nominal flow may not reach H14 efficiency at 120% of it.

None of this shows on the label. It shows up as a fan running near its limit, or a leak test result that is hard to explain.

The usual cause is ordinary. An FFU or terminal housing is selected for the airflow schedule of an earlier design revision, then asked for more air after the room layout changes. The fix is more filter area, or a written check that the rated flow still covers the new duty.

We select HEPA filters from the project's own airflow schedule and keep the rated flow in the equipment file, so a later change has something to be checked against.

Related

More on this subject

AHU casing deflection: D1 or D2

EN 1886 classes AHU casing strength by deflection at test pressure: D1 up to 4 mm/m, D2 up to 10 mm/m. On a high-static GMP supply unit, a flexing panel works its gaskets loose and leakage rises. Ask which class was tested, on what model box, and whether your design pressure fits.

InsightRead

Bag-in/bag-out: a contained filter change

In a potent-compound suite the exhaust HEPA collects the compound for its whole life. A bag-in/bag-out housing needs gas-tight isolation dampers, a bag change in which the ring never opens to the room, ports for in-place leak testing and space to work the bag, plus a written procedure and trained technicians.

InsightRead

Both states are required; only the stage is a choice

A 50 m² Grade B room needs 10 classification locations under ISO 14644-1:2015, and EU GMP Annex 1 requires them at rest against ISO 5 and in operation against ISO 7, with the smoke study in both states. Whether each run sits in OQ or PQ is for the URS and risk assessment to justify.