At 20 air changes an hour, a material airlock needs about 14 minutes for a 100:1 particle drop after the outer door closes. The interlock needs a hold-open timer and alarm for trolleys, and the countdown should start at door closure. The gowning airlock is laid out around people instead.
A 3 m/s supply jet near a pressure tap can shift the reading by up to about 5 Pa, down or up depending on its angle, which is a third to half of a 10–15 Pa cascade. Tap position, tubing without low loops, matched tube lengths and a still reference port decide whether a room pressure trend is trustworthy.
Measuring every room against one reference stops errors stacking but leaves room-pair differences at up to ±2 Pa with ±1 Pa sensors. Room-to-room sensors show airflow direction directly but add errors along the chain. Record one set, compute the other, and state the error budget.
Airflow visualization shows flow patterns over the critical zone, direction at openings and the effect of interventions. It does not show particle levels, filter integrity, velocity or microbial control, and a study filmed at rest says little about operation. Plan interventions and acceptance criteria first.
ACH is supply airflow divided by room volume: 2,400 m³/h in a 120 m³ room is 20 ACH. It is an output of the class, heat load and 100:1 recovery time the room needs. Write those into the URS, keep ACH as a check, and prove the room with particle counts and a recovery test.
A 10–15 Pa differential between grades exists only while the door is shut. Once it opens, door swing, the operator's wake and any temperature difference between rooms drive air both ways. Holding adjacent rooms at the same temperature, keeping door-open time short and interlocking airlocks keep the exchange small.