An open door between a Grade B airlock and its Grade C corridor trades air in both directions, whatever the gauge read a second earlier.
The 10–15 Pa we design between adjacent grades exists only across a closed door; Annex 1 (2022) gives a minimum of 10 Pa as its guidance value. The differential does its work through the gaps around a shut leaf. Open the door and the two rooms become one volume. The differential collapses, and the only thing still pushing air the right way is the cleaner room's surplus supply, leaving through an opening that has suddenly become very large.
Three things push the other way while it is open:
- The door leaf, which sweeps air out and draws air back as it swings.
- The operator walking through, who drags a wake of air behind them.
- Any temperature difference between the rooms. Warmer air leaves through the top of the opening and cooler air comes in along the floor, a two-way exchange the net outflow has to beat.
The third is the easiest to design out and the one most often missed. Two rooms on different AHUs, one held a couple of degrees warmer than the other, will trade air at every opening.
What helps: hold adjacent rooms at the same temperature where the process allows, keep door-open time short, and interlock the airlocks so the cleaner room never faces the corridor directly.
Industries




