A URS that asks for "20 air changes per hour" has written down the answer before anyone did the sum.
Air changes per hour is supply airflow divided by room volume. A 120 m³ room supplied with 2,400 m³/h runs at 20 ACH. The figure is real, but it is an output of the design, and the requirements that should produce it sit elsewhere:
- The cleanliness class the room must hold, at rest and in operation.
- The heat the room must lose: process equipment, lighting, people.
- How fast it must recover after a disturbance: a 100:1 recovery time to ISO 14644-3, stated in the URS with the method. (Annex 1's clean-up period, guidance under 20 minutes, is a separate figure set during qualification.)
Work those out and the airflow is whichever of them asks for the most. Sometimes that is cleanliness. In a room with a hot process it is often the heat load, and the ACH that results has nothing to do with the rule of thumb in the URS.
Written as the requirement, ACH does damage both ways. Rooms with light loads get more air than they need, and the fan energy is paid every hour of the plant's life. Rooms with heavy loads meet the ACH on paper and still fail on temperature or recovery.
Keep ACH as a sanity check on the airflow schedule. Put the class, the heat load and the recovery time in the URS, and prove them the way qualification does: particle counts and a recovery test.