  • Manufacturing & Distribution
  • 1 min read

UV-C lamps go in downstream of the cooling coil, and coil cleaning soon drops off the maintenance plan.

The reasoning sounds fair: the lamps keep the coil clean, so cleaning looks like money spent twice. The pattern we have seen is a pressure drop across the coil that keeps climbing anyway, to something like double the clean figure.

UV-C does one thing on a coil. It limits the growth of bacteria and mould on the wet surfaces the light reaches, and that growth is part of what blocks a coil. The ASHRAE Handbook reports reduced air-side pressure drop on wetted coils for that reason. The same chapter describes UV-C as a complement to conventional maintenance.

What it cannot remove is anything that was never alive. Dust that got past the filters, fibres and scale stay between the fins, and where a filter frame has been leaking they are most of the blockage.

The lamps need looking after as well. The handbook gives a typical rated life of 9,000 hours, about a year of continuous running, and notes that a blue glow does not indicate that UV-C is present. Lamps in a dusty airstream need wiping. Lamp sections should have door safety interlock switches, because UV-C injures eyes and skin.

Fitting lamps adds lines to the maintenance plan: lamp hours, a replacement date, an interlock test. The coil inspection and the pressure drop reading stay where they were.

Related

More on this subject

Vibration on AHU fans: route or online sensors

Monthly route-based vibration surveys catch slow fan faults such as imbalance, misalignment and bearing wear at a low cost per point. Permanent online sensors catch faults that develop between visits. Put sensors on fans whose stop takes a Grade A or B room out of spec with no standby, and route the rest.

InsightRead

Walk-on ceilings: service the plant from above

A walk-on cleanroom ceiling turns the void into a service floor, so dampers, sensors, cables and lighting are maintained without entering the room. It only helps filter changes if the HEPA housings are top-serviceable, and the void must be designed as a floor. Worth it for plant-heavy suites, rarely for small labs.

InsightRead