A loose lug at half load shows about a quarter of the temperature rise it would show at full load.
Heat at a bad joint rises roughly with the square of the current, so a thermal scan of lightly loaded panels finds little, and the report then says the panels are fine. On the survey report, look for these entries:
- Load at the time of the scan, per circuit. NFPA 70B (2023 edition, since replaced by the 2026 edition) says the inspection shall be performed at normal circuit loading; where that is not feasible it permits not less than 40 percent of nominal circuit loading, and the loading shall be documented.
- Line of sight. Covers were opened under the site's electrical safety procedure, or the panel has infrared windows. A camera cannot see through a steel door or a clear plastic shroud.
- Emissivity. Bare copper and aluminium reflect, and a shiny busbar can read cold while it is hot. The reading should come from a painted, taped or oxidised surface.
- A reference. Each phase is compared with the other two and with similar circuits at similar load. One absolute temperature means little.
- A record that leads somewhere: thermal and visible image, temperature difference, severity, action. Then a second scan after the repair.
Book the survey for a production day in the hot season, when chillers and AHUs draw their real current.
How loaded were your panels the last time they were scanned?