Nobody can test the URS line "alarm on low room pressure" as it is written.
It does not say at what pressure, after how long, or whether the alarm latches. The document that says so is the functional specification, the FS. Usually written by the supplier or the integrator, it describes how the system will do what the URS asks, one numbered function at a time.
EU GMP Annex 15 (2015) names it twice in section 3. The specification for equipment, facilities, utilities or systems should be defined in a URS and/or a functional specification, and before installation equipment should be confirmed to comply with the URS/functional specification at the vendor site, if applicable.
In the usual V-model each specification faces a test: URS and PQ, FS and OQ, design specification and IQ.
Without an FS, the tester watches the alarm come up after 30 seconds and writes "30 seconds" as the expected result. The system has been tested against itself.
Number every function so that a test step can cite it, and approve the FS before configuration starts. The alarm delay is a small decision. Someone who knows how long the door stays open during a material transfer has to make it, in writing, before the OQ.