GAMP 5 Second Edition puts critical thinking first

  • Life Sciences
  • 1 min read

GAMP 5 Second Edition, published by ISPE in July 2022, puts critical thinking ahead of the test script.

In practice that means scaling validation effort to the risk a function carries for patient safety, product quality and data integrity, and cutting documents that exist only to be filed. The Second Edition also adds guidance for agile development and for cloud and service-based systems, which the first edition barely touched.

On a BMS or EMS in a GMP plant, this moves the hours. The functions that carry GMP data deserve deep testing: room pressure and particle alarms, the audit trail, time synchronization, data transfer from controller to historian, backup and restore. Trend-screen colours, report layouts and a non-GMP chiller page need far less. Where the supplier has already tested a standard function well, their evidence can be assessed and used instead of repeating the test.

The trap is sequence. A risk assessment written after the test scripts tends to confirm the plan it was written to justify, and every function ends up tested to the same depth. Written first, it should leave some functions with a line of rationale and no script at all. A quick check on any package: count the functions assessed as low risk and see how many of them still carry full test scripts.

Our automation and SCADA work is delivered to 21 CFR Part 11 and Annex 11, with GAMP 5 and ALCOA+ as the frame.

Notes on automation, CSV and data integrity

Industries

Related

More on this subject

ALCOA+ on the EMS is a design requirement

Environmental monitoring and BMS data that support GMP decisions must meet ALCOA+. In practice that means individual logins, time-synchronized controllers, an audit trail users cannot disable, alarms acknowledged with name and comment, and tested backups, with GMP-critical parameters separated early onto a validated system.

Read

GMP on the electrical side

Where a SCADA, BMS or EMS records GMP-relevant data, access control, clock synchronization, alarm records and audit trails are decided by the electrical and automation engineers. Many sites keep those parameters on a separate validated EMS. Humiley's cross-functional training covers GMP, validation and project management.

InsightRead

When the SCADA admin also runs the shift

PIC/S PI 041-1 expects system administrator rights to sit apart from people who generate or approve GMP data, where possible. On small sites one engineer often does both. The conflict can be controlled: named separate accounts, admin activity reviewed by QA or IT, and configuration changes through change control.

InsightRead