In a common GDP warehouse layout, a 2–8 °C cold room sits inside a 15–25 °C store, and only the cold room has backup cooling.
The backup goes where the low setpoint is: duplicated condensing units, an alarm to a phone, the generator circuit. In Viet Nam the 15–25 °C store depends on active cooling as well, because insulation alone will not hold 25 °C through a hot afternoon. When that cooling stops, the store drifts toward outdoor temperature, and in most layouts it is the larger of the two zones.
At design stage the ambient zone deserves the review the cold room already got: a second cooling unit, standby power for it, and an alarm routed to a person with a response time written into the SOP.
Putting the cold room inside conditioned space lowers its load. Its walls and ceiling still need a continuous vapour barrier on the warm side, facing the store; without one, moisture from the store's air works into the insulation and stays there.
Door openings link the two zones in a second way. Each opening draws ambient air into the cold room, and its moisture ends up as ice on the evaporator. An anteroom or a fast-acting door cuts that ice load and the number of defrost cycles, and defrost is when top-shelf readings tend to move.
Talk to an engineer: contact@humiley.com · +84 28 7777 6668 (Viet Nam office)