2–8 °C and 15–25 °C under one roof

  • Life Sciences
  • 1 min read

In a common GDP warehouse layout, a 2–8 °C cold room sits inside a 15–25 °C store, and only the cold room has backup cooling.

The backup goes where the low setpoint is: duplicated condensing units, an alarm to a phone, the generator circuit. In Viet Nam the 15–25 °C store depends on active cooling as well, because insulation alone will not hold 25 °C through a hot afternoon. When that cooling stops, the store drifts toward outdoor temperature, and in most layouts it is the larger of the two zones.

At design stage the ambient zone deserves the review the cold room already got: a second cooling unit, standby power for it, and an alarm routed to a person with a response time written into the SOP.

Putting the cold room inside conditioned space lowers its load. Its walls and ceiling still need a continuous vapour barrier on the warm side, facing the store; without one, moisture from the store's air works into the insulation and stays there.

Door openings link the two zones in a second way. Each opening draws ambient air into the cold room, and its moisture ends up as ice on the evaporator. An anteroom or a fast-acting door cuts that ice load and the number of defrost cycles, and defrost is when top-shelf readings tend to move.

Talk to an engineer: contact@humiley.com · +84 28 7777 6668 (Viet Nam office)

Industries

Related

More on this subject

A month-end note from Tony Nguyen, CEO

After more than twenty years with automation vendors and running an EU-GMP EPC contractor, Tony Nguyen saw problems start at the handovers between companies rather than inside any one scope. This note explains why Humiley is organized as one accountable team across design, project management, equipment and maintenance.

InsightRead

A one-page-per-risk CCS storyboard

A contamination control strategy spread across dozens of documents is hard to present in one inspection day. A storyboard with one page per risk, carrying design controls, SOP references, monitoring trends, the owner and open CAPAs, gives the team a way to walk an inspector through it without rewriting the strategy.

InsightRead