Part 11 starts with the predicate rule

  • Life Sciences
  • 1 min read

Section 11.1 of 21 CFR Part 11 ties its scope to records that other FDA regulations already require you to keep.

Those regulations are the predicate rules: 21 CFR 211 for drug manufacturing, 820 for devices, and so on. FDA's 2003 guidance on Part 11 scope and application confirmed the narrow reading, covering records a predicate rule requires plus records submitted to the agency.

For a BMS or EMS, that becomes work on the points list: name the rule that requires each point's record. Room pressure differentials, temperature and RH in classified rooms, and particle counts used in batch release usually have one. Office comfort loops, chiller sequencing and most control setpoints usually do not, unless someone uses them for a GMP decision.

The list usually splits into a small GMP-critical set and a large plant-control set. Many plants move the first into a validated EMS with audit trail, access control and electronic signatures, and leave the BMS to run the plant. A whole BMS under Part 11 controls costs more to validate.

Plants exporting to Europe need one more step. EU GMP Annex 11 has no predicate-rule test; it covers computerized systems used in GMP activities, scaled by risk. The split still helps, but the BMS needs a documented risk assessment.

We write that split into the URS for monitoring and SCADA systems, before the platform is chosen.

Our automation and validation engineering

Industries

Related

More on this subject

GMP on the electrical side

Where a SCADA, BMS or EMS records GMP-relevant data, access control, clock synchronization, alarm records and audit trails are decided by the electrical and automation engineers. Many sites keep those parameters on a separate validated EMS. Humiley's cross-functional training covers GMP, validation and project management.

InsightRead

GAMP 5 Second Edition puts critical thinking first

GAMP 5 Second Edition (2022) scales validation effort to risk to patient safety, product quality and data integrity, and adds agile and cloud guidance. On a GMP BMS, test alarms, audit trail and data transfer deeply. A quick check: count low-risk functions that still carry full test scripts.

InsightRead

Keep the BMS outside the EMS validation boundary

When the BMS and the validated EMS share one platform, the validation boundary takes in the control logic and every setpoint change becomes change control. An EMS with its own sensors, database and QA alarms under Part 11 and Annex 11 allows the BMS to be managed under good engineering practice.

InsightRead