A line operator in full cleanroom gowning is comfortable at a lower room temperature than an engineer in a shirt walking the same corridor.
ISO 7730 and ASHRAE Standard 55 model comfort from two inputs, clothing insulation in clo and activity in met. Light summer office wear is around 0.5 clo. A coverall, hood, mask, gloves and boots over undergarments sits nearer the 1.0 clo of typical winter indoor clothing. For activity, ISO 7730 puts seated office work at about 1.2 met and standing light work, such as a lab or light industry, at about 1.6 met, and an operator loading and walking the line can be above that. Both inputs push the neutral temperature down.
Take the design temperature from an office comfort range and the gowned operators run warm. They sweat under the hood, adjust gowns and touch masks, and particle shedding rises with it. QA tends to see the result as an EM trend before engineering hears a comfort complaint.
The room temperature therefore belongs in the URS, set from the gowning level and the work being done and agreed with QA and EHS, before the load calculation is run. A lower room temperature raises the sensible load and, at the same RH, lowers the dew point the coil must reach. Coil size, chilled water temperature and reheat all follow from it, and a setpoint changed after the AHU is ordered leaves the coil short.