Heat pipe or electric reheat: where the energy really goes

  • News
  • 1 min read

Tropical cleanroom AHUs cool the air to wring the water out, then heat it straight back up.

That reheat is a running cost nobody puts in the tender.

Two common ways to pay for it. Electric reheat after the cooling coil is cheap to buy and easy to control, and every kilowatt of it is paid for twice: once as reheat, and once as the cooling that took that heat out.

A wrap-around heat pipe puts one section before the cooling coil and one after. The warm entering air is pre-cooled, and the heat taken from it is carried round to reheat the cold leaving air, with no pump and no energy input. The pre-cooling has a second effect: the coil spends less of its capacity on sensible cooling, so more goes to removing moisture.

The cost is air-side pressure drop, paid by the fan every hour the unit runs. Fan power is airflow times pressure drop divided by efficiency. For an example unit moving 5 m³/s, an extra 100 Pa at 60% fan efficiency is about 833 W, or roughly 7,300 kWh over 8,760 hours.

Set that against the reheat it replaces, which in a humid climate runs most of the year. The saving often wins, but it is a calculation for each unit. Many designs end up with both: heat pipe for the bulk, a small electric stage for fine control.

Our energy modeling, which targets 30% lower HVAC energy, counts reheat at design stage for this reason.

What reheat method does your newest AHU use?

Related

More on this subject

Two envelopes for a cleanroom HVAC tender

Score the technical envelope of a cleanroom HVAC tender and sign it off before any price is opened. Issue the scoring sheet with the tender: mandatory items pass or fail, the rest weighted, for example 40% technical depth and 20% each for documentation, delivery and service. Score every listed deviation.

InsightRead

Value engineering after tender: savings that return at OQ

After an over-budget cleanroom HVAC tender, three savings recur: an EN 1886 L2 casing instead of L1, fewer room pressure transmitters, and deleted door drop-seals. Each can reappear as an OQ failure in airflow, alarm testing or pressure differentials, so check every line against its URS requirement and test before accepting it.

InsightRead

Zoning and Pressure Cascade

In pharmaceutical facility design, if the HVAC system is the "lungs," then the Zoning and Pressure Cascade strategy is the "immune system." It creates invisible but effective barriers that prevent microbial ingress and strictly control…

InsightRead