Water held hot in a distribution loop sanitizes itself every minute of the day, and it pays for that in energy and in rouge.
Choosing between a hot loop and an ambient loop with periodic sanitization is one of the early decisions on a PW or WFI system, and it is hard to reverse once the pipe is welded.
A hot loop runs continuously at a temperature where microbes do not grow, commonly around 70–80 °C for WFI. Microbial control is close to automatic. The costs sit elsewhere. Heat is lost along every metre of pipe. Users that cannot take water that hot each need a sub-cooler, a small heat exchanger that grows biofilm unless it is drained and sanitized with the loop. And stainless steel in hot, high-purity water rouges faster, so derouging goes on the maintenance calendar.
An ambient loop runs near room temperature with periodic sanitization: hot water on a timed cycle, or ozone dosed into the tank and destroyed by UV before the users. Energy is lower and user points need no coolers. In exchange, the sanitization cycle becomes a validated operation, and sampling has to show the loop stays in control between cycles.
Water quality, the number of hot users and the energy price all move the answer. Humiley fixes the circulation temperature in the design basis before the P&ID is issued.
Which way did your last WFI loop go, and would you choose it again?