Around every ceiling HEPA housing there is a second joint, housing flange to ceiling panel, and the installed filter scan never looks at it.
The scan under ISO 14644-3 covers the filter media, its frame and the seal between filter and housing. The flange that holds the housing in the ceiling lies outside it, and a different trade made it on site.
Whether it matters depends on which way the air wants to go. Under a positive room with a return-air void, leakage runs out of the room and costs some pressure. Where the void is at higher pressure than the room, as over a negative containment suite or a pressurised plenum, unfiltered void air comes in beside the filter. The room's particle counts then carry the evidence without pointing at the cause.
Sealing it is simple work done carefully: a continuous gasket under the flange, compressed evenly by the fixings, and a cleanroom-grade sealant bead at the visible edge, finished so it can be wiped.
Checking it takes a particle counter and a few minutes per housing. With the system running, move the probe slowly along the flange and compare with the room background; a smoke pencil shows direction. File both with the filter scan.