Lockout/tagout on an air handling unit: the order of the steps

  • Manufacturing & Distribution
  • 1 min read

The isolator is locked off, and the fan wheel is still turning in the draught from the unit next door.

Two AHUs on a common duct do that. Air from the running unit leaks back through the stopped one and windmills its fan. A sleeve caught in the wheel does not care where the torque comes from, and a permanent-magnet EC motor that is being turned generates voltage at its terminals.

An AHU has more energy sources than its electrical supply, which is why the sequence in OSHA 29 CFR 1910.147 starts with knowing them. Local regulations apply on your site; check their steps against this order.

  1. Identify every source: fan and heater supplies, the control circuit, steam or hot water, chilled water under pressure, UV lamps, and moving air from connected systems.
  2. Shut down through the normal stop, then isolate each source: isolators open, valves closed, the duct damper shut and secured.
  3. Lock and tag. Each person working on the unit fits a personal lock and keeps the key.
  4. Release what is stored. Wait for the fan to run down and chock the wheel. Wait the discharge time marked on the drive. Vent and drain any coil that will be opened.
  5. Try to start it. Press the local start, confirm nothing happens, and test for voltage where you will work. Then open the door.

Stopping the unit from the BMS is not isolation. A fan stopped from the graphic restarts on the next schedule or the next operator click.

Industries

Related

More on this subject

VFI or VI: choosing a UPS for GMP data loads

IEC 62040-3 classes UPS by how much supply disturbance reaches the load. Double-conversion VFI units keep motor-start sags, feeder transfers and generator hunting away from EMS servers and controllers; line-interactive VI units pass some through. The cost is losses, and eco mode quietly lowers the class.

InsightRead

Vibration on AHU fans: route or online sensors

Monthly route-based vibration surveys catch slow fan faults such as imbalance, misalignment and bearing wear at a low cost per point. Permanent online sensors catch faults that develop between visits. Put sensors on fans whose stop takes a Grade A or B room out of spec with no standby, and route the rest.

InsightRead