If checking a bag filter means stopping the AHU and opening a door, the monthly inspection turns into a glance at the pressure gauge.
Gauges tell you a filter is loading. They do not show a bag that has collapsed against its neighbour, a frame gasket that has slipped, water standing in the drain pan or a fan belt starting to fray. A technician sees those in seconds through a viewing window with a light behind it, while the unit runs and the rooms downstream keep their pressure.
On a hygienic AHU that means a window and an internal light in the sections that fail quietly: the filter sections, the coil and drain pan, the humidifier and the fan. The light switch sits outside with an indicator, so nobody leaves it burning. Fittings are sealed and cleanable, so they do not become a contamination source of their own.
Two cautions. A window in a cold section is a thermal bridge and will sweat in a humid plant room unless it is double-glazed with a thermally broken frame. And a window does not replace the door: some checks still need the unit stopped and the section opened under a permit.
At Humiley the maintenance strategy is built from the project's own asset register. That register is the place to ask, component by component, whether the inspection can be done with the unit running, and to put a window wherever the answer should be yes.