Grade D fixes the particle limit of a tablet compression room and a cream manufacturing room, and very little else about them.
Grade D is ISO 8 at rest. That sets the cleanliness the room must reach. It says nothing about what the process puts into the air, and in a site that makes both tablets and creams, that is where the design splits.
In granulation and compression the product itself is the contaminant. Powder must not reach the corridor, so the room is usually kept as a pressure sink or protected by a sink or bubble airlock. Local exhaust sits at the dust points, and return air is filtered before any recirculation.
The cream room next door has little dust. Its load comes from jacketed vessels, hot water and steam, which add sensible and latent heat, and from washing down floors and walls. The effort goes into vapour exhaust over the vessels, a cooling coil sized for that heat gain, finishes and panel joints that survive water and detergent, and drains that do not compromise the grade.
Copying the airflow schedule from one room to the other because the grade matches is one of the most common shortcuts we find in inherited designs. Before any airflow is copied, fill in the process part of the room data sheet: dust sources, vessel duties, how often the room is washed.