On most GMP sites the split between OEM service and the in-house team is drawn by the warranty, then left alone for years after it ends.
During the warranty that split makes sense. The chiller maker's conditions usually reserve the refrigerant circuit, the compressor and the controls for its own technicians.
The cost arrives later, when the same contract is renewed out of habit. The OEM visits quarterly to change filters the site team could change weekly, and a chiller that trips on a night shift waits for a technician who may be hours away.
A better split follows the tools and skills each job needs. Compressor overhaul, refrigerant leak repair and recharge, controller firmware, and oil or vibration analysis where the OEM holds the baseline stay with the OEM. Filters, belts and bearings, coil and drain-pan cleaning, ΔP and temperature trending, and the first response to a trip belong to the people who are on site every day.
GMP adds two conditions whoever holds the spanner. An OEM visit to an AHU serving a classified room goes through the site's permit and change control. And the service report is filed in the site CMMS against the asset tag, because an inspector asks for the asset's history, not the vendor's portal.
Our maintenance service covers criticality-based planned maintenance, spares and asset registers, and 24/7 response across Southeast Asia under a maintenance agreement.
Which chiller tasks does your site still wait for the OEM to do?