A pallet of devices leaves the EtO steriliser still giving off ethylene oxide, and it keeps doing so for hours or days in the aeration room.
That room gets less design attention than the steriliser, yet it is the one operators walk into. Ethylene oxide is classed as a human carcinogen and is flammable from about 3% in air. Its occupational exposure limits are set in parts per million, far below anything a nose can detect.
So the ventilation brief starts from the operator. Air goes through once, with no recirculation back to the room or to any other space, whatever that costs at the chiller. The room is held negative to the corridor so leakage runs inward. Extract is taken low, because EtO vapour is heavier than air, and supply is arranged to sweep across the pallets instead of leaving still pockets between racks. Aeration is often run warm to speed off-gassing, which also raises the release rate.
The exhaust then has to go somewhere acceptable. Emission rules in many markets require abatement, a catalytic oxidiser or a wet scrubber, and the fan and ductwork have to suit the gas.
Fixed EtO detectors at breathing height, tied to door access and alarms, close the loop. Operators should see the room's reading before they open the door.
We write the extract rate and room pressure into the device plant's HVAC design basis next to the steriliser data.