One check we make on every AHU walk-down before a package goes to qualification: the condensate trap under the cooling coil.
In a draw-through unit the coil section runs under negative pressure, so the drain has to push water out against suction. If the trap's water seal is shallower than the suction it has to hold, air is pulled in through the drain instead. The pan does not empty, and water backs up until it spills into the casing or the next section.
The arithmetic is short. 500 Pa of negative static pressure is about 51 mm of water column, and the seal needs to be deeper than that with margin, plus enough outlet leg for the water to leave. A trap detail copied from a comfort-cooling drawing is often too shallow for a cleanroom unit with high filter pressure drops.
On the walk-down we look at the seal depth against the section pressure on the datasheet, the fall to the drain, and whether the trap can be primed and cleaned. It takes a couple of minutes. A flooded drain pan found during OQ costs a deviation and a retest.
It is one line on the turnover checklist. A package goes to qualification when every such line is closed and recorded, so IQ starts from a verified installation instead of an open punch list.